Fire Rated

Fire Rated Universal part no.
0071

For individual installation in cable structures and working spaces.

1

Optical fiber

2

Stainless steel tube

3

Armor of steel wires

4

Halogen-free jacket

High resistance to crushing load (more than 571 lb/in) which is retained after the fire

Minimum combustible content

Remains functional under direct flame for at least 180 minutes

Withstands physical impact and water used during fire-fighting

Small size – thin, light, economical

Suitable for all applications

Up to 48 fibers in a tube

Diameter less than 0.39

Max installation tension 899 lb
Crush — from 571 lb/in
Fiber count up to 24 up to 36 up to 48 up to 72 up to 96
Cable diameter, in 0.346 0.362 0.374 0.39 0.409
Cable weight, lb/ft 0.103 0.112 0.12 0.13 0.142
Min bending radius, in 5.197 5.433 5.61 5.846 6.142
Max installation tension 1574 lb
Crush — from 571 lb/in
Fiber count up to 24 up to 36 up to 48 up to 72 up to 96
Cable diameter, in 0.378 0.378 0.39 0.406 0.425
Cable weight, lb/ft 0.132 0.131 0.14 0.149 0.16
Min bending radius, in 5.669 5.669 5.846 6.083 6.378
Start shopping
Operation temperature -76°F … 158°F
Installation temperature 14°F … 122°F
Transportation and storage temperature -58°F … 122°F
Minimum bending radius 10x cable diameter
Life time 25 years