InSky OPGW

InPhase OPPC Optical Phase Conductor (OPPC)

An effective aerial solution when OPGW or ADSS cannot be used.

1

Optical fiber

2

Stainless steel tube

3

Aluminum-clad steel wire

4

Aluminum alloy wire

4

Aluminum alloy wire

Up to 288 fibers

ACS wires are highly corrosion-resistant

Effective solution to provide redundancy in harsh conditions, such as long cable spans, crossings of cable spans, power lines with previously installed OPGW and ADSS and others

InPhase OPPC (Optical Phase Conductor) is an optimal solution to provide redundancy in harsh conditions, such as long cable spans, crossings of cable spans, power lines with previously installed OPGW and ADSS and others. InPhase OPPC cable does not increase the load on support towers. It can be used as a backup or independent communication channel.

The main application of InPhase OPPC is the transmission of electrical power and construction of extensive optical communication system for data transmission. It can have up to 288 fibers and is highly corrosion-resistant. The rated breaking strength (RBS) range can be from 3,372 to 44,962 lb.

Outer layers of InPhase OPPC are made of aluminum alloy wire which effectively removes heat from a lightning stroke point and increases short-circuit current resistance. It can also be used for distributed acoustic sensing (DAS) and distributed temperature monitoring (DTS) to prevent third-party intervention, detect place of lightning strike and short circuit.

Fiber count, up to 288
Rated breaking strength (RBS), lb 3372...44962
Cable diameter, in 0.394...1.339
Cable weight, lb/ft 0.134...1.344
Cross-sectional area, in² 0.078...0.775
Operating temperature -58°F ... +185°F
* -76°F ... +185°F upon request
Installation temperature -22°F ... +122°F
Transportation and storage temperature -58°F ... +185°F
Minimum bending radius 20 x cable diameter
Design life 50 years
Operating temperature -58°F ... +185°F
Installation temperature -22°F ... +122°F
Transportation and storage temperature -58°F ... +185°F
Minimum bending radius 20 x cable diameter
Design life 50 years
Operating temperature -76°F ... +185°F
Installation temperature -22°F ... +122°F
Transportation and storage temperature -76°F ... +158°F
Minimum bending radius 20 x cable diameter
Design life 50 years
Warranty period of operation определяется договором поставки, но не менее двух лет empty