InAir Self-Supporting

InAir ADSS Light Aramid (Multi-Tube Aramid Single Jacket Cable) part no.
0059

Designed for aerial installation on transmission towers, high voltage power lines and railway catenary; highly resistant to electromagnetic effect.

1

Central strength member (dielectric fiberglass reinforced plastic)

4

Water-blocking yarns

2

Optical fiber

3

PBT loose tube filled with water-blocking gel

4

Water-swellable yarns

5

Reinforcing member – aramid yarns

6

Jacket

7

Ripcord

All-dielectric construction – fully resistant to electromagnetic fields

Dry construction – easy to strip

Reduced weight and size. Low ice and wind load

Cost-effective design

Aerial installation on distribution and transmission lines up to 138kV

Maximum rated design loads up to 2248 lb with span lengths up to 656 ft

Wide range of operating temperatures. Installation temperature down to -22 F

Maximum rated design loads (MRDL) 337 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.299 0.327 0.362 0.394
Cable weight, lb/ft 0.029 0.034 0.041 0.047
Min bending radius, in 4.488 4.921 5.433 5.906
Maximum rated design loads (MRDL) 450 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.299 0.327 0.362 0.394
Cable weight, lb/ft 0.03 0.034 0.041 0.047
Min bending radius, in 4.488 4.921 5.433 5.906
Maximum rated design loads (MRDL) 674 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.307 0.331 0.362 0.394
Cable weight, lb/ft 0.031 0.035 0.041 0.047
Min bending radius, in 4.606 4.961 5.433 5.906
Maximum rated design loads (MRDL) 899 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.425 0.449 0.472 0.496
Cable weight, lb/ft 0.06 0.066 0.071 0.078
Min bending radius, in 6.378 6.732 7.087 7.441
Maximum rated design loads (MRDL) 1349 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.429 0.449 0.472 0.496
Cable weight, lb/ft 0.061 0.066 0.071 0.078
Min bending radius, in 6.457 6.732 7.087 7.441
Maximum rated design loads (MRDL) 1574 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.429 0.453 0.476 0.5
Cable weight, lb/ft 0.061 0.067 0.073 0.079
Min bending radius, in 6.457 6.811 7.165 7.52
Maximum rated design loads (MRDL) 1798 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.433 0.457 0.476 0.5
Cable weight, lb/ft 0.062 0.068 0.073 0.079
Min bending radius, in 6.496 6.85 7.165 7.52
Maximum rated design loads (MRDL) 2248 lb
Crush — from 171 lb/in
Fiber count up to 48 (6х8) up to 72 (6х12) up to 96 (6х16) up to 144 (6х24)
Cable diameter, in 0.441 0.461 0.484 0.508
Cable weight, lb/ft 0.065 0.07 0.076 0.082
Min bending radius, in 6.614 6.929 7.283 7.638
Start shopping
Operation temperature -76°F … 158°F
Installation temperature -22°F … 122°F
Transportation and storage temperature -76°F … 158°F
Minimum bending radius 15x cable diameter
Life time 25 years
Warranty as specified in the supply agreement, min 2 years